VFDs for Pumps and Fans: Energy Savings, Harmonics and Heat Derating

17.11.26 10:28 AM

In short: for centrifugal pumps and fans, flow varies with speed, but power varies roughly with the cube of speed. Running at 80 percent speed instead of throttling can cut power by around half. That is why variable frequency drives (VFDs) pay back quickly on variable-flow pumps, cooling tower fans and air handling units. Drives also bring issues to manage: harmonic currents on the supply, motor insulation stress, and derating in high ambient temperatures. BTGC supplies Danfoss VACON low and medium voltage drives.

Danfoss VACON AC drives range

Water transmission and distribution, district cooling, desalination, HVAC and process cooling are major energy users in the Kingdom. Saudi energy efficiency programmes and rising tariffs make speed control on these loads one of the clearest efficiency upgrades.

Where the savings come from

  • Affinity laws: flow is proportional to speed, head to speed squared and power to speed cubed.

  • Throttling a valve or damper wastes the extra head; reducing speed removes it.

  • Savings are largest where the load varies widely and runs long hours; systems with high static head save less.

  • Soft starting reduces mechanical stress and inrush current, extending pump and motor life.

Harmonics and power quality

SolutionTypical result
6-pulse drive with DC or AC chokeBasic reduction; current distortion often 30 to 45 percent
Passive harmonic filterCurrent distortion reduced to around 5 to 10 percent
Active front end (low harmonic drive)Current distortion below about 5 percent; can also regenerate
12- or 18-pulse with phase-shifting transformerCommon on medium voltage and large low voltage drives

IEEE 519 sets harmonic limits at the point of common coupling, and utilities in the Kingdom may set their own requirements. A harmonic study during design avoids overheating of transformers and cables, nuisance trips and interference with other equipment.

Desalination plant pumping station

Installing drives in hot climates

  • Most drives are rated for 40 to 50 °C; above that they must be derated or oversized, so specify the real room temperature.

  • Cool electrical rooms properly; heat from drives can be large at full load.

  • Use IP-rated enclosures and filters against dust; keep heat sinks clean.

  • Use motors suitable for inverter duty, and dV/dt or sine filters for long cables to protect insulation and bearings.

  • Check bearing currents on larger motors; insulated bearings or shaft grounding may be needed.

Danfoss VACON from BTGC

Danfoss Drives supplies VACON and VLT low and medium voltage AC drives for pumps, fans, compressors and process machines. BTGC is the Danfoss VACON partner in Saudi Arabia. See also MV soft starters or VFDs, the electrical power systems page and the power and utilities sector page.

Questions buyers ask

Does a VFD always save energy? Only where the load varies. A pump running at constant full flow gains little and the drive adds small losses.

Can an existing motor run on a VFD? Often yes, after checking insulation, cooling at low speed and bearing currents.

Can BTGC do a savings estimate? Yes, from the duty profile, pump curves and running hours.