Instrument and Plant Air Quality: Dryers, Filters and ISO 8573-1 Classes

17.11.26 02:18 PM

In short: control valves, positioners, actuators and analysers depend on clean, dry instrument air. Water, oil and particles in the air cause sticking positioners, corroded actuators and false trips. ISO 8573-1 defines air quality classes for particles, water (pressure dew point) and oil, and the right combination of compressor, dryer and filters delivers the required class. Hot, humid summers in the Kingdom make drying the hardest part. BTGC supplies Ingersoll Rand compressors, dryers and filters.

Ingersoll Rand air compressor

Every refinery, petrochemical plant, gas facility and power plant in the Kingdom has an instrument air system, often backed up by plant air. Loss of instrument air can shut down a whole unit.

ISO 8573-1 in brief

ContaminantHow it is classed
Solid particlesBy particle count and size
WaterBy pressure dew point, for example minus 40 degC for a very dry class
OilBy total oil content, including vapour and aerosol

Dryer and filter options

  • Refrigerated dryers: economical, dew point a few degrees above zero; suitable for plant air.

  • Desiccant (adsorption) dryers: dew points of minus 40 degC or lower for instrument air; heatless or heated regeneration.

  • Heat of compression dryers: use compressor heat to regenerate desiccant on oil-free compressors.

  • Coalescing and particle filters before and after dryers to remove oil aerosols and dust.

  • Oil-free compressors avoid oil contamination at source.

Process plant

Hot climate and maintenance points

  • Size dryers for summer inlet temperature and humidity, not catalogue reference conditions.

  • Install dew point sensors and alarm on high dew point.

  • Change filter elements on differential pressure and replace desiccant on schedule.

  • Drain condensate reliably with zero-loss drains and check them often.

  • Keep air receivers and headers sloped and drained.

Ingersoll Rand from BTGC

Ingersoll Rand makes compressed air and gas equipment, including centrifugal and oil-free compressors, dryers and filters. BTGC is the Ingersoll Rand partner in Saudi Arabia. See also aeration blowers, turbo compressors for plant air and the oil and gas sector page.

Questions buyers ask

What dew point does instrument air need? Many plants specify about minus 40 degC pressure dew point, or at least well below the lowest ambient temperature.

Is a refrigerated dryer enough for instrument air? Often not; desiccant dryers are usually specified for instrument air.

Can BTGC audit our compressed air system? Yes, including air quality and energy use.

Contact BTGC

Email info@btc-ksa.com or call +966 13 856 0528. Branches: Dammam, Jubail and Yanbu. Request a quote.