In short: a synchronous motor needs all the protection of a large induction motor, plus functions for its starting winding and its excitation. During starting, the damper winding carries heavy current and can overheat if the motor stalls or starts too often. Once running, loss of field or a sudden overload can pull the motor out of step, causing pulsating torques and currents that damage the machine and its driven equipment. Correct protection and excitation settings prevent this. BTGC supplies Electric Machinery synchronous motors and services them in Jubail.

Synchronous motors drive reciprocating and centrifugal compressors, large water transmission pumps and mills across the Kingdom. Protection gaps usually show up as damaged damper bars, rotor faults or trips during voltage dips.
Protection functions to check
| Function | Protects against |
|---|---|
| Starting and stall protection | Damper winding overheating during long or repeated starts |
| Incomplete sequence | Failure to synchronise within the allowed time |
| Field loss | Running without excitation, drawing reactive power |
| Pull-out or out-of-step | Loss of synchronism from overload or voltage dips |
| Exciter and diode monitoring | Failed rotating diodes or exciter faults |
| Standard motor functions | Overcurrent, differential, earth fault, unbalance, thermal |
Settings and coordination
Base starting limits on the manufacturer data for damper winding thermal capacity.
Set the number of starts per hour and cooling time between starts.
Coordinate excitation control with pull-out protection for voltage dips.
Check that field application happens at the correct speed and rotor angle.
Review settings after any change to the driven load or supply system.

Testing and maintenance
Test protection relays and trip circuits at planned intervals.
Record starting current and time trends to spot rising load or supply problems.
Inspect damper bars and rotor connections during overhauls.
Check rotating diodes and exciter windings in brushless machines.
Analyse every trip before restarting the motor.
Electric Machinery from BTGC
Electric Machinery, part of the WEG group, builds synchronous motors and generators for pumps, compressors and power generation. BTGC is the Electric Machinery partner in Saudi Arabia, with full electric motor services at the Jubail service center. See also synchronous motors for compressors, brushless exciters and the power and utilities sector page.
Questions buyers ask
What happens if a synchronous motor loses its field? It loses synchronism and draws large reactive current, which can damage the motor.
Why limit the number of starts? Each start heats the damper winding; too many starts can crack or melt bars.
Does BTGC service synchronous motors? Yes, at the Jubail service center, with Electric Machinery support.
Contact the BTGC power division
Email power@btc-ksa.com or call +966 13 856 0528. Branches: Dammam, Jubail and Yanbu. Request a quote.