In short: the oil in a power transformer records what is happening inside it. Dissolved gas analysis (DGA) detects overheating and electrical faults long before they trip the unit, and moisture, acidity and breakdown voltage show how fast the insulation is ageing. BTGC supplies HD Hyundai Electric power transformers in Saudi Arabia and supports owners with monitoring and life-extension planning.

A power transformer at a Saudi industrial substation works hard: high ambient temperatures, heavy and sometimes harmonic-rich loads, and dust on the radiators. Its life is set by the paper insulation, and paper ages fastest when it is hot, wet and in acidic oil. The good news is that the oil carries the evidence, and sampling it is cheap compared with any failure.
What DGA tells you
| Gas | Typical cause |
|---|---|
| Hydrogen (H2) | Partial discharge, the earliest sign of electrical stress |
| Methane, ethane | Low-temperature overheating of oil |
| Ethylene | Higher-temperature overheating, for example a hot joint or core fault |
| Acetylene (C2H2) | Arcing; any rising trend needs urgent attention |
| Carbon monoxide and dioxide | Overheating or ageing of paper insulation |
Interpretation uses ratio methods such as the Duval triangle and IEC 60599. The trend matters more than a single value: a stable gas level in an old transformer may be normal, while a doubling between two samples is a warning even if the absolute value is low.
The other oil tests
Moisture in oil and the estimated moisture in paper: wet paper ages faster and lowers dielectric strength.
Breakdown voltage: a quick check of contamination.
Acidity and interfacial tension: show oil oxidation and sludge formation.
Furan analysis: estimates the remaining strength of the paper insulation.

A sensible monitoring programme
Annual DGA and oil tests on all power transformers, more often for critical or ageing units.
Online DGA monitors on generator step-up and critical plant transformers.
Radiator and fan cleaning before summer, because high top-oil temperature accelerates ageing.
Oil reclamation or drying when acidity or moisture trends up, before sludge forms on the windings.
HD Hyundai Electric from BTGC
HD Hyundai Electric builds power transformers, GIS and switchgear for utilities and industry. BTGC is the HD Hyundai Electric partner in Saudi Arabia, supporting specification, supply and life-cycle planning for new and installed units. See the related articles on power transformer specification and gas-insulated switchgear, and the power and utilities page.
Questions buyers ask
How often should DGA be done? At least yearly for most power transformers; quarterly or online for critical or suspect units.
Can a transformer with high acetylene stay in service? That depends on the level and trend; a rising acetylene trend needs an urgent engineering assessment and often a shutdown inspection.
Does BTGC supply online DGA monitors? Monitoring options are specified with new HD Hyundai Electric transformers; ask BTGC for retrofit options for installed units.
Contact the BTGC power division
Email power@btc-ksa.com or call +966 13 856 0528. Branches: Dammam, Jubail and Yanbu. Request a quote.