In short: plants often buy a bigger compressor when pressure drops, but the real cause may be leaks, poor piping or users running at higher pressure than they need. A compressed air audit logs flow, pressure and power over one or two weeks, finds leaks and waste, and shows the real demand profile. Only then can the right compressor size and control be chosen. BTGC supplies Ingersoll Rand compressors and blowers with maintenance support.

Compressed air is one of the most expensive utilities in a plant, and Saudi summers push compressors to their limits.
What an audit measures
| Item | Why |
|---|---|
| Flow over time | Shows base load, peaks and night demand |
| Pressure at compressors and users | Reveals pressure drop in piping and treatment |
| Power and loading of each compressor | Shows efficiency and wasted unloaded running |
| Leaks | Often a large share of total demand |
| Air quality | Moisture, oil and particles against what users need |
Common findings
Leaks at hoses, fittings and drains wasting a large share of air.
Header pressure set higher than any user needs.
Open blowing, cleaning with air guns and other low-value uses.
Undersized pipes and clogged filters causing pressure drop; see piping design.
Several compressors part-loaded instead of one well-loaded machine.

Turning results into action
Fix leaks first, then re-measure demand.
Reduce pressure step by step while watching users.
Size new compressors for the measured profile, with base-load and trim machines.
Add storage and sequencing controls; see compressed air energy savings.
Repeat audits every few years or after plant changes.
Ingersoll Rand from BTGC
Ingersoll Rand makes centrifugal air compressors and blowers. BTGC supplies Ingersoll Rand in Saudi Arabia with spare parts and maintenance support. See also compressor rooms in hot climates and the petrochemicals sector page.
Questions buyers ask
How long should an audit run? Usually one to two weeks, covering normal production and weekends.
Can leaks really be that large? Yes, in older plants leaks are often one of the largest single users of air.
Do I need to stop production for an audit? No, loggers are fitted while the plant runs.
Contact BTGC
Email info@btc-ksa.com or call +966 13 856 0528. Branches: Dammam, Jubail and Yanbu. Request a quote.