Valves for District Cooling Networks

17.11.26 03:15 PM

In short: district cooling plants make chilled water centrally and pump it through buried networks to buildings, which is common for large developments in the Kingdom. The network needs isolation valves for sections and branches, air valves at high points, drain valves at low points, and control or balancing valves at energy transfer stations. Valves must stay tight with low leakage for decades, because chilled water losses cost energy and water treatment chemicals. BTGC supplies AVK and AVK SVMC valves for water networks.

AVK valves made in Saudi Arabia

New cities, airports, campuses and mixed-use developments in the Kingdom increasingly use district cooling to cut electricity use. Network reliability depends on valves that are easy to find, operate and maintain.

Valves in a district cooling network

LocationTypical valve
Plant headers and large mainsButterfly valves with gearboxes or actuators
Branch and building connectionsResilient-seated gate or butterfly valves
High pointsAir release and vacuum valves
Low pointsDrain valves
Energy transfer stationsControl and balancing valves

Selection points

  • Pressure rating including surge; see water hammer.

  • Epoxy coating inside and out and stainless steel stems and bolts for long life underground.

  • Insulation and anti-condensation measures for valve chambers.

  • Low-leakage seats so isolated sections hold during repairs.

  • Access chambers sized for operation and maintenance.

Cooling plant serving a district cooling network

Operation and maintenance

  • Exercise isolation valves regularly and record turns.

  • Check air valves; trapped air reduces flow and raises pumping energy.

  • Inspect chambers for water ingress and corrosion.

  • Keep valve positions and locations in the network GIS.

  • Coordinate valve work with water treatment to avoid contamination.

AVK from BTGC

AVK of Denmark makes valves, hydrants and fittings for water, wastewater and gas; AVK SVMC manufactures in the Kingdom. BTGC is the AVK partner in Saudi Arabia. See also water network valves, chiller compressor oils and the power and utilities sector page.

Questions buyers ask

Why do district cooling networks need air valves? Air pockets reduce flow and cause noise and corrosion; air valves release them at high points.

Butterfly or gate valves for chilled water? Butterfly valves suit large mains; gate valves are common on smaller branches.

Does BTGC supply locally made valves? Yes, through AVK SVMC in the Kingdom.

Contact the BTGC valve team

Email valves@btc-ksa.com or call +966 13 856 0528. Branches: Dammam, Jubail and Yanbu. Request a quote.