In short: it seems odd to worry about water in a hot country, but condensation is a common cause of panel failures in the Kingdom. Coastal sites such as Jubail, Dammam and Yanbu have very humid air, desert nights cool panels quickly, and over-cooled air-conditioned panels drop below the dew point when doors open. Water then forms on terminals and electronics, causing corrosion, tracking and trips. Small heaters controlled by hygrostats or thermostats, good sealing and sensible cooling set points prevent it. BTGC supplies Pfannenberg enclosure heaters, controls and cooling units.

Outdoor marshalling cabinets, drive panels, telecom shelters, pump station panels and switchgear in coastal and desert sites are all at risk.
When condensation forms
| Situation | Why |
|---|---|
| Humid coastal nights | Panel surfaces cool below the dew point of the air |
| Large day and night swings | Air inside cools and releases moisture |
| Over-cooled panels | Cooling units set too low create cold surfaces |
| Doors opened in humid weather | Warm, wet air meets cold equipment |
| Wash-down and rain | Water enters through poor seals and glands |
Prevention measures
Install anti-condensation heaters sized for the enclosure volume.
Control heaters with hygrostats or thermostats so they run only when needed.
Seal doors, cable glands and unused openings.
Set cooling units to a reasonable temperature, often around 35 degC, not as low as possible; see enclosure cooling.
Drain condensate from cooling units away from the panel.

Inspection tips
Look for corrosion, white deposits and tracking marks on terminals.
Check heater operation and control settings.
Inspect door gaskets and glands for damage.
Use humidity loggers in problem panels to understand the pattern.
Record faults linked to humid seasons.
Pfannenberg from BTGC
Pfannenberg of Germany makes enclosure cooling units, heaters, filter fans, process chillers and signalling devices. BTGC is the Pfannenberg partner in Saudi Arabia. See also signalling devices, IP ratings and the electrical power systems page.
Questions buyers ask
Why do panels need heaters in a hot country? To keep internal surfaces above the dew point at night and in humid weather.
Should panel cooling be set as low as possible? No, over-cooling creates cold surfaces and condensation.
Does BTGC supply enclosure heaters? Yes, Pfannenberg heaters, hygrostats and thermostats.
Contact the BTGC power division
Email power@btc-ksa.com or call +966 13 856 0528. Branches: Dammam, Jubail and Yanbu. Request a quote.