Enclosure Heat Load: How to Size Panel Cooling

18.11.26 01:14 PM

In short: sizing enclosure cooling starts with the heat that must be removed: losses from drives, power supplies and other equipment inside, plus heat flowing in through the walls when the outside is hotter than the panel. In Saudi summers, ambient and solar gain can be as large as the internal load. The total, compared with the target internal temperature, decides whether filter fans are enough or an air conditioner or air-to-water exchanger is needed. BTGC supplies Pfannenberg enclosure cooling.

Pfannenberg enclosure cooling units

Drive panels, MCCs and control cabinets in the Kingdom often sit in plant rooms or outdoors at 45 °C and above.

The parts of the heat load

SourceHow to estimate
Internal lossesAdd up equipment losses from data sheets; drives typically lose a few percent of their power as heat
Heat through the wallsEnclosure surface area x heat transfer coefficient x temperature difference
Solar gainExtra load for outdoor panels in sun; shading cuts it a lot
MarginFuture equipment and dust on coils and filters

Choosing the cooling method

  • Filter fans: only when outside air is always cooler than the target inside temperature, and clean enough.

  • Air-to-air heat exchangers: a closed loop, but still need outside air cooler than inside.

  • Enclosure air conditioners: cool below ambient, the usual choice when ambient exceeds the target, as in Saudi summers.

  • Air-to-water heat exchangers: for high loads where chilled or cooling water is available.

AC drives installed in control panels

An example in words

  • A drive panel with 2 kW of internal losses, a target of 35 °C and an ambient of 50 °C also gains heat through its walls, so the cooler must remove more than 2 kW.

  • Filter fans cannot work here, because the outside air is hotter than the target.

  • An air conditioner sized for the total load at 50 °C ambient is needed, not one sized at a standard rating point.

  • Check capacity at the real ambient, since cooling capacity falls as ambient rises.

Pfannenberg from BTGC

Pfannenberg makes enclosure air conditioners, air-to-water heat exchangers, filter fans and process chillers. BTGC supplies Pfannenberg in Saudi Arabia and helps select the right unit. See also cooling electrical panels, condensation in enclosures and thermal management and cooling.

Questions buyers ask

What temperature should a panel be kept at? Much equipment is rated for about 35 to 40 °C inside the enclosure; check the equipment data.

Are filter fans ever enough in Saudi Arabia? Sometimes in air-conditioned rooms; outdoors in summer, usually not.

Does dust reduce cooling? Yes, clogged filters and coils cut capacity, so plan regular cleaning.