In short: a stationary battery only proves itself when the mains fail, so its condition must be checked before that moment. Routine inspections and voltage and temperature checks catch obvious problems, internal resistance trends flag weak cells, and a timed discharge test measures the real capacity. Batteries are typically replaced when capacity falls to around 80 percent of rating, per standards such as IEEE 450. BTGC supplies Hoppecke stationary batteries for substations, UPS and DC systems.

Substations, control rooms, telecom sites and oil and gas facilities in the Kingdom depend on batteries for protection, controls and emergency lighting. Heat shortens battery life, so testing matters even more here.
What to check and how often
| Check | Typical frequency |
|---|---|
| Visual, float voltage, room temperature | Monthly |
| Cell voltages and electrolyte (vented types) | Quarterly |
| Internal resistance or conductance trending | Quarterly to yearly |
| Connection torque and thermography | Yearly |
| Discharge capacity test | At acceptance, then periodically and more often as capacity falls |
Discharge capacity testing
Follow the relevant standard: IEEE 450 for vented lead-acid, IEEE 1188 for VRLA and IEEE 1106 for nickel-cadmium.
Discharge at a set current or power to the specified end voltage, timing the result.
Correct for temperature and compare with the rated capacity.
Record weak cells and check their connections.
Plan replacement when capacity approaches the replacement limit.

Extending battery life
Keep battery rooms cool; every rise above about 25 degC shortens lead-acid life.
Use temperature-compensated charging where recommended.
Do not mix old and new cells in one string.
Keep terminals clean and connections tight.
Choose battery types suited to the site temperature; see batteries in Saudi heat.
Hoppecke from BTGC
Hoppecke of Germany makes industrial batteries for utilities, oil and gas and telecom, and traction batteries for material handling. BTGC is the Hoppecke partner in Saudi Arabia. See also DC battery systems, traction batteries and the power and utilities sector page.
Questions buyers ask
How often should a battery capacity test be done? At acceptance and then periodically, more often as the battery ages or loses capacity.
When should a battery be replaced? Commonly when capacity drops to about 80 percent of rating.