In short: gas plants and refineries remove hydrogen sulphide from gas and recover it as liquid sulphur in sulphur recovery units. Molten sulphur must stay within a narrow temperature window: too cold and it solidifies in valves and lines, too hot and it becomes very viscous. Valves in sulphur service are therefore steam-jacketed, with designs that leave no cold spots or pockets where sulphur can freeze. Jacketed plug valves are a common choice. BTGC supplies Xomox jacketed and sleeved plug valves.

The Kingdom produces very large amounts of sulphur from sour gas processing and refining, much of it exported. Sulphur handling lines run continuously and blocked valves can stop sulphur production and force gas plants to cut rates.
Why molten sulphur is difficult
Sulphur melts at about 115 to 120 degC and must be kept above this everywhere in the line.
Its viscosity rises sharply above about 160 degC, so overheating also causes problems.
Dissolved H2S in sulphur is toxic and released when sulphur is agitated or cooled.
Solid sulphur builds up in cavities and seats, jamming valves.
Valve features for sulphur service
| Feature | Purpose |
|---|---|
| Full steam jacket on body and bonnet | Keeps every wetted surface above the freezing point |
| Cavity-free design such as sleeved plug valves | No pockets where sulphur can collect and solidify |
| Steam-jacketed flanges and connections | Avoid cold spots at joints |
| Suitable sealing materials | Resist sulphur and H2S at operating temperature |
| Corrosion-resistant materials where water is present | Wet sulphur and sulphur acids attack carbon steel |

Operation and maintenance
Check steam supply, traps and jacket temperatures regularly.
Never let jacketed lines cool with sulphur inside; drain or keep heated.
Follow H2S safety precautions when opening sulphur equipment.
Inspect sleeves and seals at shutdowns and clean out deposits.
Keep spare jacketed valves for critical positions.
Xomox from BTGC
Xomox, part of Crane ChemPharma and Energy, supplies sleeved and jacketed plug valves, lined valves and high-performance butterfly valves. BTGC is the Xomox partner in Saudi Arabia. See also sour service valves, lubricated and sleeved plug valves and the oil and gas sector page.
Questions buyers ask
Why do sulphur valves need steam jackets? To keep sulphur above its freezing point everywhere inside the valve.
What happens if sulphur overheats? Above about 160 degC it becomes very viscous, slowing flow and increasing pressure drop.
Does BTGC supply jacketed valves? Yes, Xomox jacketed plug valves for sulphur service.
Contact the BTGC valve team
Email valves@btc-ksa.com or call +966 13 856 0528. Branches: Dammam, Jubail and Yanbu. Request a quote.