In short: refineries, petrochemical complexes, steel and aluminium plants and desalination sites often generate their own power with steam or gas turbines driving synchronous generators. The generator's excitation system controls voltage and reactive power, and its protection must cope with both grid-connected and island operation. Good specification, protection settings and maintenance keep this captive power reliable. BTGC supplies Electric Machinery synchronous generators and motors.

Captive and cogeneration plants in the Kingdom supply steam and power to large industrial sites, often running in parallel with the grid and able to island when the grid is lost. Generator trips at these sites can stop whole production units.
Key parts of a synchronous generator system
Stator winding that delivers power at medium or high voltage.
Rotor field winding supplied with DC by a brushless exciter with rotating diodes.
Automatic voltage regulator controlling voltage, reactive power or power factor.
Cooling system: open air, closed air with air-to-water coolers, or other designs depending on size.
Bearings, lubrication and vibration monitoring.
Typical protection functions
| Function | Protects against |
|---|---|
| Differential protection | Internal winding faults |
| Loss of excitation | Field failure that makes the generator absorb reactive power |
| Reverse power | Motoring of the generator when the prime mover fails |
| Over and under frequency or voltage | Abnormal system conditions, especially in island mode |
| Stator and rotor earth fault | Insulation failures to earth |
| Negative sequence | Unbalanced loads heating the rotor |

Maintenance and testing
Test stator insulation, polarisation index and partial discharge at planned outages.
Inspect exciter diodes, fuses and connections; check the AVR settings and response.
Inspect stator wedges, end windings and cooling coolers for contamination and leaks.
Trend vibration, bearing temperatures and winding temperatures.
Test protection relays and trip circuits on a schedule; see DC supplies for protection.
Electric Machinery from BTGC
Electric Machinery, part of the WEG group, builds synchronous generators and motors for industrial power, compressor and pump drives. BTGC is the Electric Machinery partner in Saudi Arabia, with full electric motor and generator services at the Jubail service center. See also synchronous motors for compressors, steam turbine and generator overhaul planning and the power and utilities sector page.
Questions buyers ask
Why do generators in captive plants need island-mode protection? When the grid is lost, frequency and voltage can swing widely; protection and controls must keep the island stable or trip safely.
What does a brushless exciter avoid? Carbon brushes and slip rings on the main field, reducing maintenance.
Can BTGC repair generators? Yes, at the Jubail service center, including rewinds and rotor repairs.
Contact the BTGC power division
Email power@btc-ksa.com or call +966 13 856 0528. Branches: Dammam, Jubail and Yanbu. Request a quote.