In short: a standard six-pulse drive draws current in pulses, adding harmonic currents that heat transformers and cables, disturb other equipment and can break utility limits. Mitigation ranges from simple DC chokes to 12- or 18-pulse transformers, passive and active filters, and active front end drives with near-sinusoidal input current. The right choice depends on how much of the load is on drives and the limits at the point of supply. BTGC supplies Danfoss VACON drives and options.

Water pumping stations, HVAC and district cooling plants, desalination and mining sites in the Kingdom often have most of their load on drives.
Mitigation options
| Method | Typical result | Notes |
|---|---|---|
| DC or AC chokes | Lower distortion than a bare drive | Low cost; often built into drives |
| 12- or 18-pulse | Large reduction with phase-shifting transformers | Suits large single drives |
| Passive filters | Tuned reduction of main harmonics | Check for resonance and light-load behaviour |
| Active filters | Cancel harmonics for groups of drives | Good for retrofits and mixed loads |
| Active front end (AFE) drives | Very low input distortion and regeneration | Higher cost; ideal for large or regenerative loads |
Planning the study
Check the share of drive load on each transformer and the short-circuit level at the point of common coupling.
Compare predicted distortion with IEEE 519 or the utility's grid code limits.
Watch for resonance with power factor capacitors, which can amplify harmonics.
Include standby generators, where harmonics are more severe.

In operation
Measure harmonics after commissioning and after adding drives.
Check transformer and cable temperatures in summer.
Keep filter capacitors and fans maintained.
For energy savings and heat derating, see VFDs for pumps and fans.
Danfoss VACON from BTGC
VACON drives, part of Danfoss Drives, include air- and liquid-cooled drives with low-harmonic and active front end options. BTGC supplies Danfoss VACON in Saudi Arabia with options and spares. See also drive retrofits and the electrical and power systems page.
Questions buyers ask
Do small drives need filters? Usually not one by one, but many small drives together can exceed limits.
What is an active front end? A drive input stage using switching transistors instead of diodes, giving low harmonics and the ability to regenerate.
Can harmonics damage transformers? They add heating, so heavily loaded transformers may need derating or a K-rated design.