In short: many plants in the Kingdom still run variable speed drives installed 15 or 20 years ago. Once spare parts and support end, a single failure can stop a pump, fan or conveyor for weeks. Planning replacements before failure, with checks on the motor, cables, harmonics, controls and cooling, turns a risky emergency into a short planned outage, and usually brings energy and diagnostic gains too. BTGC supplies Danfoss VACON and VLT drives for retrofits.

Water, power, oil and gas and industrial plants have large fleets of low voltage drives from many generations and makers. Obsolescence often goes unnoticed until a drive fails.
Retrofit planning steps
| Step | What to do |
|---|---|
| Inventory | List drives, ratings, age, makers and support status |
| Risk ranking | Rank by process criticality and spare availability |
| Site survey | Check motors, cables, space, cooling and control interfaces |
| Design | Select drives, filters and options, and plan the cutover |
| Commissioning | Transfer parameters, tune, test and train staff |
Technical checks
Motor insulation and bearings: older motors may need dv/dt or sine filters; see bearing currents.
Cable length and type, and earthing arrangements.
Harmonic limits at the point of connection; see harmonics.
Control signals, fieldbus and safety functions such as safe torque off.
Panel cooling for summer ambient; see enclosure cooling.

Making the switch smooth
Record old drive parameters and process settings before removal.
Pre-assemble and test panels to shorten outages.
Replace drives in groups to standardise spares.
Train operators and technicians on the new drives.
Keep a few spare units for the most critical services.
Danfoss VACON from BTGC
Danfoss Drives supplies VACON and VLT drives for pumps, fans, conveyors, cranes and hoists. BTGC is the Danfoss VACON partner in Saudi Arabia. See also drives for mining, drives for cranes and the electrical power systems page.
Questions buyers ask
When should an old drive be replaced? Ideally before support and spare parts end, based on criticality and failure risk.
Can the existing motor be kept? Often yes, after checking insulation, bearings and the need for filters.
Does BTGC help with drive retrofits? Yes, with Danfoss drive selection and supply.
Contact the BTGC power division
Email power@btc-ksa.com or call +966 13 856 0528. Branches: Dammam, Jubail and Yanbu. Request a quote.