Control Valve Seat Leakage Classes: ANSI/FCI 70-2 Class II to VI

18.11.26 02:32 PM

In short: control valves are built to regulate flow, not always to shut off tight, so their seat leakage is graded in classes defined by ANSI/FCI 70-2 (and IEC 60534-4). Class IV is common for metal seats, Class V for tight metal seats and Class VI for soft seats. Asking for a tighter class than needed adds cost and actuator size, while asking for too little can waste energy or erode trims. BTGC supplies KOSO control valves and tests valves at its Jubail service center.

KOSO severe service control valves

Process and power plants in the Kingdom specify control valve leakage on every data sheet, often without knowing what the class means in practice.

The classes in brief

ClassAllowed leakage (summary)Typical seat
II0.5% of rated capacityMetal, double-seated valves
III0.1% of rated capacityMetal, balanced trims
IV0.01% of rated capacityMetal seats, common default
VVery small water leakage per inch of port diameter per psiTight metal seats, high thrust
VIBubbles per minute of air, by port sizeSoft seats

Choosing the class

  • Use Class IV where the valve throttles and a separate block valve isolates.

  • Ask for Class V where leakage wastes high-pressure fluid, erodes the seat or affects safety, such as boiler feedwater and high-pressure drop duties.

  • Use Class VI soft seats only within their temperature and media limits.

  • Remember that tighter classes need more actuator thrust to seat the plug.

Valve test bench at the BTGC Jubail service center

Testing and service

  • Seat leakage is tested at the factory and again after repairs, using the method in the standard.

  • Damaged trims leak more over time; plan overhauls before leakage harms the process; see control valve overhaul.

  • For isolation valves, different standards apply; see API 598 and ISO 5208.

  • Review sizing when duty changes; see control valve sizing.

KOSO from BTGC

Nihon KOSO makes control valves and actuators known for severe service trims. BTGC supplies KOSO in Saudi Arabia with sizing support and spares, and tests valves at the Jubail service center.

Questions buyers ask

Is Class VI always better? No; soft seats have temperature and erosion limits, and metal seats with Class V may suit hard duties better.

Can a valve meet a tighter class after repair? Sometimes, with new trim and lapping; the actuator must still give enough thrust.

Can BTGC test leakage on site valves? Valves can be tested at the BTGC Jubail service center.

Contact the BTGC valve team

Email valves@btc-ksa.com or call +966 13 856 0528. Branches: Dammam, Jubail and Yanbu. Request a quote.