In short: three different properties are often confused. Flame-retardant cables limit the spread of fire along a cable run. Low-smoke zero-halogen (LSZH) cables give off little smoke and no corrosive halogen gas when they burn, which protects people and electronics. Fire-resistant cables keep working for a stated time in a fire, so alarms, emergency lighting, fire pumps and smoke fans stay powered. Projects often need all three. BTGC supplies Bahra Electric cables made in Saudi Arabia.

Hospitals, metro stations, tunnels, high-rise buildings, control rooms and process facilities all have rules on how cables behave in a fire.
Three properties, three purposes
| Property | What it means | Typical test standards |
|---|---|---|
| Flame-retardant | Fire does not spread far along single or bunched cables | IEC 60332-1 and IEC 60332-3 |
| Low smoke, zero halogen | Little smoke and no halogen acid gases | IEC 61034 and IEC 60754 |
| Fire-resistant (circuit integrity) | Keeps power or signals running in a fire for a set time | IEC 60331, BS 6387 or BS 8491, per the specification |
Where each is used
LSZH: enclosed public spaces, tunnels, data centres and control rooms, where smoke and corrosive gas are the main danger.
Fire-resistant: fire alarm, emergency lighting, fire pump, smoke extraction, emergency shutdown and other critical circuits; see fire pumps.
Flame-retardant PVC: general plant power where halogen-free cable is not required and cost matters.
Process plants: the owner's specification sets the type per area, so follow the project cable schedule.

Specifying and installing
State the property and the test standard, not just fire cable.
Fire resistance applies to the whole circuit, so use supports, glands and joints that keep it working in a fire.
Check current ratings, since fire barriers and grouping change derating; see cable derating in hot climates.
Keep fire-resistant and normal circuits separated where the design requires it.
For buildings, check the Saudi Building Code and the approving authority.
Bahra Electric from BTGC
Bahra Electric is a Saudi manufacturer of power, control and instrumentation cables and busways. BTGC supplies Bahra Electric cables in Saudi Arabia for plants and projects; ask BTGC for the fire-performance constructions available. See also control and instrumentation cables, the electrical and power systems page and mega-projects and EPC.
Questions buyers ask
Is an LSZH cable automatically fire-resistant? No. LSZH describes smoke and gas; fire resistance is a separate circuit-integrity property.
Do fire-resistant cables cost more? Yes, they have extra insulation layers, so use them on the circuits that need them.
Are locally made cables accepted on Saudi projects? Local content is encouraged on many projects; approval depends on the owner's vendor list.
Contact the BTGC power division
Email power@btc-ksa.com or call +966 13 856 0528. Branches: Dammam, Jubail and Yanbu. Request a quote.