Pressure and Temperature Switches: Set Points, Deadband and Reliability

18.11.26 09:00 AM

In short: pressure and temperature switches open or close an electrical contact when a set value is reached. They are simple, need no power for the sensing element and are still widely used for alarms, pump and compressor protection and local trips. Choosing the right range, deadband and contact type, protecting the switch from vibration and pulsation, and proof testing it regularly make the difference between a reliable trip and a nuisance. BTGC supplies Nuova Fima pressure and temperature switches.

Nuova Fima instruments

Compressors, pumps, boilers, lube oil systems and utility packages across Saudi plants rely on switches. Many nuisance trips and missed alarms trace back to poor selection or testing.

Key terms

TermMeaning
Set pointThe value where the contact changes state
DeadbandDifference between switching on rising and falling values
RepeatabilityHow closely the switch trips at the same value each time
Proof pressureMaximum pressure the switch can withstand without damage
Contact ratingVoltage and current the contact can switch

Selection points

  • Choose a range where the set point sits near the middle, not at the ends.

  • Match deadband to the process; too small causes chatter, too large delays reset.

  • Use gold-plated contacts for low-power PLC inputs and silver contacts for higher loads.

  • Select certified housings for hazardous areas.

  • Protect sensors with snubbers or diaphragm seals in pulsating or corrosive service; see diaphragm seals.

Process plant

Testing and reliability

  • Proof test trip switches at intervals set by the safety assessment.

  • Test both trip and reset values and record as-found and as-left results; see calibration.

  • Mount switches away from strong vibration.

  • Consider transmitters with diagnostics for important safety functions; see pressure transmitters.

  • Replace switches that drift or stick.

Nuova Fima from BTGC

Nuova Fima of Italy makes pressure gauges, transmitters, switches, thermometers and diaphragm seals for oil and gas, petrochemical and power plants. BTGC is the Nuova Fima partner in Saudi Arabia. See also thermowells and the petrochemicals sector page.

Questions buyers ask

What causes a pressure switch to chatter? Pulsation or vibration near the set point with too small a deadband.

Should trip switches be replaced by transmitters? For many safety functions, transmitters with diagnostics are preferred, but switches remain common.

Does BTGC supply hazardous area switches? Yes, Nuova Fima switches with suitable certifications.

Contact BTGC

Email info@btc-ksa.com or call +966 13 856 0528. Branches: Dammam, Jubail and Yanbu. Request a quote.